AS/NZS 3599 Part 1 Mv Aerial Bundled Conductor ABC Overhead Cables

Model NO.: AL/XLPE/CWS/HDPE, Al/XlPE /HDPE
Wire Core Material: Al
Certification: CCC, CE
Model: Al/XLPE/Cws/HDPE,Al/XLPE /HDPE
Brand: Jl
Rated Voltage: 6.35/11 Kv,12.7/22 Kv
Refer Standard: AS/NZS 3599
Trademark: JL
Transport Package: Wooden Drum/Steel Drum
Specification: 10-300 mm2
Origin: Jiangsu, China
HS Code: 76149000
Model NO.: AL/XLPE/CWS/HDPE, Al/XlPE /HDPE
Wire Core Material: Al
Certification: CCC, CE
Model: Al/XLPE/Cws/HDPE,Al/XLPE /HDPE
Brand: Jl
Rated Voltage: 6.35/11 Kv,12.7/22 Kv
Refer Standard: AS/NZS 3599
Trademark: JL
Transport Package: Wooden Drum/Steel Drum
Specification: 10-300 mm2
Origin: Jiangsu, China
HS Code: 76149000
MV Aerial Bundled Conductor ABC Cables Standards:
IEC 60502 / AS/NZS 3599-1 standards
MV Aerial Bundled Conductor ABC Cables Constructions:
AS/NZS 3599 Part 1 Mv Aerial Bundled Conductor ABC Overhead Cables


Conductor: Round, Aluminium Conductor
Conductor Screen: Extruded semi-conductive layer.
Insulation:  XLPE
insulation Screen: Extruded semi-conductive layer.
metallic Screen(optional): Copper wire screen or copper tape screen.
Separator: Semi-conductive swellable tape.
outer Sheath: HDPE.
Messager wire: Galvanized steel wires.
Assembly: Three XLPE insulated screened cores are bundled around the galvanized steel
wires in a right hand lay.

MV Aerial Bundled Conductor ABC Cables Application:
Aerial bundled cables are mainly used for secondary overhead lines on poles or as feeders
to residential premises.
The Function of messenger wire:
A) It acts as load bearing wire.    B) It acts as earth or neutral conductor
MV Aerial Bundled Conductor ABC Cables Specifications: 
AS/NZS 3599 Part 1 6.35/11 kV AL/XLPE /CWS/HDPE Screened Cables
Number of CoresxNominal Cross Section Phase Conductor Messenger Suspension Unit Continuous current rating at 30ºC ambient temp
Stranding Nominal Sectional Area Maximum Conductor Resistance Stranding Nominal Sectional Area Breaking Load
No.×mm2 mm mm mm mm No.×mm mm2 KN
3x35 6.9 3.4 0.8 1.2 7/4.75 52.4 1370
3x50 8.1 3.4 0.8 1.2 7/4.75 54.6 1530
3x70 9.7 3.4 0.8 1.2 7/4.75 57.8 1790
3x95 11.4 3.4 0.8 1.2 7/4.75 61.3 2100
3x120 12.8 3.4 0.8 1.2 19/3.50 67.3 2540
3x150 14.2 3.4 0.8 1.2 19/3.50 70.1 2840
3x185 15.7 3.4 0.8 1.2 19/3.50 73.1 3190

AS/NZS 3599 Part 1 12.7/22 kV AL/XLPE /HDPE Non-screened Cables
Number of CoresxNominal Cross Section Diameter of Conductor Thickness of Insulation Thickness of Insulation Screen Thickness of Sheath Messenger Suspension Unit Stranding Nominal Sectional Area Breaking Load
No.×mm2 mm mm mm mm No.×mm mm2 KN
3x35 6.9 5.5 0.8 1.2 7/4.75 61 1780
3x50 8.1 5.5 0.8 1.2 7/4.75 63.3 1970
3x70 9.7 5.5 0.8 1.2 7/4.75 66.5 2260
3x95 11.4 5.5 0.8 1.2 7/4.75 69.9 2600
3x120 12.8 5.5 0.8 1.2 19/3.50 75.9 3070
3x150 14.2 5.5 0.8 1.2 19/3.50 78.7 3390
3x185 15.7 5.5 0.8 1.2 19/3.50 81.7 3760

AS/NZS 3599 Part 1 12.7/22 kV AL/XLPE /CWS/HDPE Screened Cables
Number of CoresxNominal Cross Section Diameter of Conductor Thickness of Insulation Thickness of Insulation Screen Copper Wire Screen Stranding Thickness of Sheath Galvanized Steel Wire Stranding Nominal Sectional Area Breaking Load
No.×mm2 mm mm mm No.×mm mm No.×mm mm2 KN
No.×mm2 mm mm mm No.×mm mm No.×mm mm2 KN
Light Duty Screen
3x35 6.9 5.5 0.8 25/0.85 1.8 7/2.00 62.7 2280
3x35 6.9 5.5 0.8 25/0.85 1.8 19/2.00 66.7 2580
3x50 8.1 5.5 0.8 25/0.85 1.8 19/2.00 69 2780
3x70 9.7 5.5 0.8 25/0.85 1.9 19/2.00 72.6 3110
3x95 11.4 5.5 0.8 25/0.85 1.9 19/2.00 76 3460
3x120 12.8 5.5 0.8 25/0.85 2 19/2.00 79.2 3810
3x150 14.2 5.5 1 25/0.85 2 19/2.00