Grounding resistance of power equipment for effective grounding system
cycle | Claim | Description | |||
2) It is possible to extend or shorten the cycle according to the results of the grounding network excavation inspection. |
I- short-circuit current flowing into the ground via the grounding grid, A; R - the maximum grounding resistance considering the seasonal variation, Ω; | 1) When measuring the grounding resistance, such as the minimum necessary pole 2) In areas with high soil resistivity, the grounding resistance is as a. The contact voltage and step voltage are not more than allowed. b. Does not occur outside the high potential and low potential C.3~10kV valve arrester does not work 3) before the preventive test or every 3 years and when necessary |
Grounding of power equipment for non-effectively grounded systems
cycle | Claim | |
2) It is possible to extend or shorten the cycle according to the results of the grounding network excavation inspection. | 1) When the grounding grid is grounded with equipment of 1kV and below, the grounding resistance R≤120/I 2) When the connection network is only above 1kV, the grounding resistance R≤250/I 3) In any of the above cases, the grounding resistance should generally not exceed 10Ω Where: I- short-circuit current flowing into the ground via the grounding grid, A; R- taking into account the seasonal variation of the maximum grounding resistance, R; |
Grounding resistance of line tower with overhead ground wire
cycle | Claim | Description | |||
2) Other line towers are not more than 5 years | When the height of the tower is below 40m, according to the following requirements, if the tower height reaches or exceeds 40m, take 50% of the following values, but when the soil resistivity is greater than 2000Ω·m, the grounding resistance is difficult to reach 15Ω and can be increased to 20Ω. |
| |||
Soil resistivity Ω·m | Grounding resistance Ω | ||||
100 and below | 10 | ||||
100~500 | 15 | ||||
500~1000 | 20 | ||||
1000~2000 | 25 | ||||
More than 2000 | 30 |
XB2-B Series Pushbutton Switch
XB2-B series Pushbutton Switch are using controlling circuit of AC voltage up to 660V/AC 50Hz.and DC voltage below 400V.It is used for controlling signal and interlocking purposes.The main body of the push buttons adopts Circuit head,with chromium plated metal bezel,Complete units with screw and captive cable clamp connections.The contact adopts special silver alloy in order to enjoy the benefit of high anti-electrical erosion.The signal lamp series are suitable for electrical applicances circuit of AC voltage up to 380V/50Hz,and DC voltage below 380V.It is ideal for using as indicating signals,warning signals,emergency signals.