Grounding device test selection scheme

Grounding resistance of power equipment for effective grounding system

cycle Claim Description





1) no more than 6 years

2) It is possible to extend or shorten the cycle according to the results of the grounding network excavation inspection.



R≤2000/I or R≤0.5Ω, in the formula (I>4000A);

I- short-circuit current flowing into the ground via the grounding grid, A;

R - the maximum grounding resistance considering the seasonal variation, Ω;

1) When measuring the grounding resistance, such as the minimum necessary pole
The soil resistivity in the range is basically uniform, and various types can be used.
Compensation method, otherwise, the transport method should be adopted

2) In areas with high soil resistivity, the grounding resistance is as
The specified value requirement is allowed when the technical economy is extremely unreasonable.
There are a large number. But measures must be taken to ensure
When a ground short occurs, on the grounding network

a. The contact voltage and step voltage are not more than allowed.
Numerical value

b. Does not occur outside the high potential and low potential

C.3~10kV valve arrester does not work

3) before the preventive test or every 3 years and when necessary
Check the value/value and verify the thermal stability of the device grounding down conductor.

Grounding of power equipment for non-effectively grounded systems

cycle Claim



1) no more than 6 years

2) It is possible to extend or shorten the cycle according to the results of the grounding network excavation inspection.

1) When the grounding grid is grounded with equipment of 1kV and below, the grounding resistance R≤120/I

2) When the connection network is only above 1kV, the grounding resistance R≤250/I

3) In any of the above cases, the grounding resistance should generally not exceed 10Ω

Where: I- short-circuit current flowing into the ground via the grounding grid, A;

R- taking into account the seasonal variation of the maximum grounding resistance, R;

Grounding resistance of line tower with overhead ground wire

cycle Claim Description







1) 1 to 2 years of towers within 1-2km of the power plant or substation

2) Other line towers are not more than 5 years

When the height of the tower is below 40m, according to the following requirements, if the tower height reaches or exceeds 40m, take 50% of the following values, but when the soil resistivity is greater than 2000Ω·m, the grounding resistance is difficult to reach 15Ω and can be increased to 20Ω.







For towers with a height of less than 40 m, if the soil resistivity is high and the grounding resistance is difficult to drop to 30 Ω, 6 to 8 radial grounding bodies or continuous elongated grounding bodies with a total length of not more than 500 m can be used, and the grounding resistance can be unrestricted. . However, for poles with a height of 40m or more, the grounding resistance should not exceed 20Ω.

Soil resistivity Ω·m

Grounding resistance Ω

100 and below

10

100~500

15

500~1000

20

1000~2000

25

More than 2000

30

XB2-B Series Pushbutton Switch

XB2-B series Pushbutton Switch are using controlling circuit of AC voltage up to 660V/AC 50Hz.and DC voltage below 400V.It is used for controlling signal and interlocking purposes.The main body of the push buttons adopts Circuit head,with chromium plated metal bezel,Complete units with screw and captive cable clamp connections.The contact adopts special silver alloy in order to enjoy the benefit of high anti-electrical erosion.The signal lamp series are suitable for electrical applicances circuit of AC voltage up to 380V/50Hz,and DC voltage below 380V.It is ideal for using as indicating signals,warning signals,emergency signals.